AHU Sizing Guide

Unit SizeExternal WidthExternal HeightStandard Base HeightHigh Volume (3m/s)Mid Volume (2.5m/s)Optimum Volume (2m/s)
1750590740.510.430.34
2750830740.840.700.56
31050830741.381.150.92
41250950741.851.721.38
51350950742.281.91.52
613501110742.662.321.86
713501190743.022.522.02
813501350743.402.942.35
914501350903.893.222.58
1015501350904.163.502.80
1116501350904.623.783.02
1217501350904.754.063.25
1319501350905.354.623.70
1419501430905.944.953.96
1519501670907.065.894.71
16255014301408.056.715.36
17255016701409.597.996.39
182550203014011.999.997.99
193200203014015.3612.8010.24
203200239014018.4415.3612.29
213200263014020.4817.0713.66
223800263014022.9719.1415.31
234400263014027.2922.7418.19
245000263014031.6126.3421.07
255600263014035.9329.9423.95
266200263014040.2533.5426.83
276200280014040.2533.5426.83
Approximate Component Section LengthsApproximate Component Section Weights
Notes:
  • Dimensional restrictions may dictate a higher velocity of around 3m/s. This, however, is likely to mean that the air handling unit specific fan power will exceed Building Regulations requirements.
  • Subject to external static pressure and internal components, Building Regulations requirements may be met at an air handling unit velocity of 2m/s.
Instructions:
  • Choose velocity required (3m/s = red, 2.5m/s = orange, 2m/s = green)
  • Select volume required from table (or next highest value)
  • Read off Unit Size, External Width and External Height from left hand columns
  • Add base height to external unit height and 50mm for pitched roof if the unit will be sited in an external location